Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
P108
Motor Overload 100 30 {%} 100
P109
Motor Overload
Type
0 0 Speed Compensation
Ir
100%
60%
30 f
1
0
V0108
1 No Speed Compensation
P110
Start Method 0 0 Normal
1 Start on Power-up Drive will automatically start when
power is applied.
2 Start with DC Brake When start command is applied, drive
will apply DC braking according to
P174, P175 prior to starting the motor
3 Auto Restart Drive will automatically restart after
faults, or when power is applied.
4 Auto Restart with DC Brake Combines settings 2 and 3
5 Flying Start/Restart #1 Drive will automatically restart after
faults, or when power is applied.
After 3 failed attempts, drive will
Auto Restart with DC brake.
P110 = 5: Performs speed search,
starting at Max Frequency (P103)
P110 = 6: Performs speed search,
starting at the last output frequency
prior to faulting or power loss
If P111 = 0, a ying START is
performed when a start command
is applied.
6 Flying Start/Restart #2
motor current rating
P108 =
SM2 output rating
x 100
Example: motor = 3 amps; SM2 = 4
amps; P108 = 75%
Note
Do not set above the rated motor current as listed on the motor
dataplate. The motor thermal overload function of the SM2 is UL
approved as a motor protection device. If line power is cycled, the
motor thermal state is reset to cold state. Cycling power after an
overload fault could result in signicantly reducing the motor life.