19
11.4 PRESET SPEEDS AND SPEED POT
(WITH TWO-WIRE START/STOP CONTROL)
NOTES:
1. For preset speed control, all or some of the TB-13 terminals must be programmed as preset
speed selects. If only two or three preset speeds are required, only two of the TB-13 terminals
must be used. Refer to the table in the description of Parameters 31-37 in Section 15.0.
2. Program the PRESET SPEEDS (Parameters 31-37) to the desired values.
3. If speed pot control is desired when none of the preset speeds are selected (all preset speed
selects are open to TB-11), set STANDARD SPEED SOURCE (Parameter 05) to 0-10 VDC
(03).
1 2 5 6 11 13A 13B 13E 25
16 17
MAINTAINED
RUN/STOP
CONTACT
SPEED
POT
FORM A
RELAY
RUN
SIGNAL COMMON
0-10 VDC INPUT
SPEED POT POWER SUPPLY
DIGITAL INPUT REFERENCE
TB-13A FUNCTION SELECT
(PRESET SPEED #1)
TB-13B FUNCTION SELECT
(PRESET SPEED #2)
TB-13E FUNCTION SELECT
(PRESET SPEED #3)